HVAC Duct Design

MERV ratings explained: what a higher filter rating does to airflow

What a MERV rating measures, common home ratings, and how a higher-MERV filter raises static pressure and can reduce airflow depending on size and blower.

Quick answer: MERV measures how well a filter captures particles between 0.3 and 10 microns, on a scale of 1 to 16 for home filters. A higher MERV usually means more resistance to airflow, which shows up as higher static pressure across the filter. Whether that cuts airflow depends on the filter’s size and depth, how dirty it is, and your blower motor. The EPA suggests MERV 13 or as high as your system can accommodate.

What MERV measures

The EPA says MERV reports an air filter’s ability to capture particles between 0.3 and 10 micrometres, using a test method developed by ASHRAE. Its table runs from MERV 1 to 16, with HEPA as a separate category that removes at least 99.97 percent of 0.3 micrometre particles. A few steps:

  • MERV 1 to 4: capture under 20 percent of the largest particles tested (3 to 10 micrometres).
  • MERV 8: at least 70 percent of 3 to 10 micrometre particles, and at least 20 percent of 1 to 3 micrometre particles.
  • MERV 13: at least 50 percent of the smallest particles tested (0.3 to 1 micrometre), at least 85 percent of 1 to 3 micrometre and at least 90 percent of 3 to 10 micrometre.
  • MERV 16: at least 95 percent in all three ranges.

For all rating systems, the EPA says a higher rating means higher removal efficiency for most particle sizes.

Typical home ratings

The EPA advises choosing a filter rated at least MERV 13, or as high as your system’s fan and filter slot can accommodate. It says most furnaces and HVAC systems can accommodate MERV 13 without equipment problems, as long as the filter is replaced frequently, and that you may want an HVAC technician to confirm. The Building America Solution Center (PNNL) gives other reference points: MERV 6 is the ENERGY STAR minimum and MERV 8 is required by Zero Energy Ready Home and Indoor AirPlus. Filters commonly come in thicknesses of 1 to 5 inches, and the EPA suggests replacing them about every 60 to 90 days.

What a higher MERV does to static pressure

A filter is resistance in the air path, and it counts against the system’s pressure budget. We explain that budget in duct friction rate, where the filter comes off the available static pressure before the ducts get any. The Building America page says the filter is typically 20 to 50 percent of a system’s total pressure drop, and that most residential systems work well at a total external static pressure of about 0.4 to 0.5 inches of water column.

Numbers from the sources we read:

  • Typical ranges: PNNL says MERV 7 to 14 filters run from 0.05 to 0.3 iwc, depending on thickness and air velocity.
  • Depth: at 300 feet per minute, PNNL lists three MERV 7 filters at 0.20 iwc for 1 inch, 0.13 for 2 inches and 0.12 for 4 inches. A 4-inch MERV 12 filter is about 0.2 iwc at 300 feet per minute and 0.35 at 500.
  • Field measurements: a Green Building Advisor article by Allison Bailes cites Stephens and colleagues’ Austin study, where the filter drop was about 0.10 iwc for MERV below 4, 0.19 for MERV 8 and 0.32 for MERV 11. It also notes ACCA’s design protocol assumes 0.10 iwc across the filter, while a California study of 34 systems averaged 0.28.
  • Not a straight line. PNNL cites testing where the jump comes from moving off a basic 1-inch fiberglass filter to a pleated one, and deeper pleats lower the drop without changing the MERV.

What it does to airflow

It depends on the blower.

  • PSC motors do not speed up to hold airflow. PNNL says airflow falls as pressure rises. Bailes’s article cites tests where high-MERV filters cut airflow by about 7 and 11 percent in two systems.
  • ECM motors raise speed and power to hold airflow. Airflow stays steady across a wide pressure range, but fan energy rises, and PNNL warns motor burnout is more likely with an ECM when static pressure is too high.

The ACHR News article by David Springer, on Building America tests, found the airflow loss between a MERV 2 and a MERV 13 filter on PSC systems was under 200 CFM and called the energy effect almost insignificant, while warning that the drop can more than triple when a filter is fully loaded with dirt. So sources disagree on how serious it is. ACHR calls it not likely severe until the filter loads, while PNNL and Green Building Advisor stress the risk. Airflow per ton is what your cooling capacity relies on, so see CFM per ton for why losing airflow matters. PNNL lists reduced airflow as a cause of lower efficiency, duct sweating or an icing evaporator coil in humid climates, and furnace overheating.

How to use a higher MERV without choking the system

  • More filter area. Bigger or deeper filters lower the velocity and the drop. In the ACHR tests a 25 percent larger filter cut the drop of one filter from about 0.32 to 0.20 iwc at 492 feet per minute, and doubling the area cut it to about 0.07. PNNL suggests a return box holding two filters side by side.
  • Check the manufacturer’s data. PNNL says to avoid makers who do not publish static pressure data.
  • Measure total static pressure. PNNL recommends measuring it after installation and keeping the total at or below 0.4 to 0.5 iwc.
  • Replace on time. A loaded filter has far higher resistance.

Frequently asked questions

What does MERV measure?

How well a filter captures particles between 0.3 and 10 micrometres, on a scale of 1 to 16 for home filters.

Which MERV should I use at home?

The EPA suggests at least MERV 13, or the highest your system can handle. Ask an HVAC technician if you are unsure.

Does a higher MERV reduce airflow?

It usually raises resistance. Airflow loss depends on filter size, how dirty it is and your blower motor, and ECM motors hold airflow better than PSC motors.

How much static pressure does a filter use?

Roughly 0.05 to 0.3 iwc for MERV 7 to 14 filters according to PNNL, and the filter is typically 20 to 50 percent of the system’s total.

Sources

HVAC Duct Design

Sizes round and rectangular ducts from airflow and friction rate, then totals the pressure drop of a whole run.

See HVAC Duct Design